DESCRIPTION: | This model is a variation of the standard Model RP60-2A whereby the normal AC output is "frozen" at a -72VDC level. |
INPUT POWER: | 103-132/206-264VAC, 47-63Hz (jumper selected), via an IEC 320 connector on the assembly |
DC OUTPUTS: | OUTPUT VOLTAGE -48V -72V |
OUTPUT CURRENT 1A 0.25A |
REGULATION LINE LOAD 0.1% 1% 1% 6% |
OUTPUT RIPPLE(P-P) 1% 1% |
THERMAL LIMITING | Allows the -72VDC output to provide up to 0.5A output loading for 10 second periods. |
OUTPUT ISOLATION: | Both DC outputs are referenced to common and are isolated from chassis ground. |
CURRENT LIMITING: | Both outputs have current limiting with full protection and automatic recovery. |
OUTPUT INDICATOR: | A green LED indicates that both outputs are operating. |
TEMPERATURE RANGE: | Ambient temperature range is 0 to 50 degrees C for full load operation. |
CONSTRUCTION: | Enclosed assembly with removable cover. |
OUTPUT CONNECTOR: | AMP #1-480701-0 |
OUTPUT PIN ASSIGNMENTS: | 1)-72VDC, 2)Common, 3)-48VDC |
SIZE & WEIGHT: | 5.10"H x 7.90"L x 2.70"W - About 2 lbs. |
EMI DESIGN STANDARDS: | FCC20780, Class A and EN55022, Class A |
SAFETY DESIGN STANDARDS: | UL 1950, CSA C22.2-950, EN60950 |
AGENCY APPROVALS: | Model RP60-2A has received UL recognition, File #E140410, CSA certification, File #LR85037-3, EN60950 Report #D210754901. |